I'm with an APC UPS, model Back-UPS Pro 1500, which is displaying "F05" error, and constant whistle. To repair I need the electric plate (640-3078A-Z_REV07) and service manual. Thanks if anyone can help me.
Hi I also have F05 error . My local Apc service center tells me the unit is NOT repairable . I am thinkin that if I can locate the charging board/unit I should be able to replace it or have it replaced ?
I have a Back-UPS Pro 900 from 2012 (BR900GI) that has failed with an F05 error. A local APC service center has quoted me $85 (labour included) for the board replacement. I have no idea what the board number for my model would be, but the 640-3078A-Z_REV07 mentioned above seems to cost about $75 second-hand.
I'd love to keep using this device, but given the fact that a repair and a new battery are needed (it's 4 years old) ... buying a new one may seem a better option? I hate it when this happens!!
I simply put in a new battery and problem solved. I tested by putting old, bad battery in another known working unit. It immediately showed F05. New battery tested in both units. No errors. This was in a Pro 1500.
crwdns2947414:01crwdne2947414:0
Here's the user manual: Back-UP Pro 1300/1500 Installation & Operation