I have this same problem on the same unit.  It was low on R134a refrigerant.  I found two common leak points on the interior evaporator, on is at the evaporator to copper lines and the other is the temp sensor clipped to the aluminum evaporator line.  I found a hole in the line from the steel clip rubbing on the line.  I removed the clip and sensor, put epoxy over the hole and placed the sensor into the epoxy as well, and let cure for 24 hours.  Fixed after recharging.